Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/10/2010

Applicant:

ORCHARDS AT ARIZONA II LLC

Description:

Full Fire Prevention Inspection. Ray Campas--- 887-0532

Outstanding Inspections

Case Number: T10FR02378
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
11/10/2010 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required IFC 308.3 Open flame. A person shall not utilize or allow to be utilized, an open flame in connection with a public meeting or gathering for purposes of deliberation,worship, entertainment, amusement, instruction, education, recreation, awaiting transportation or similar purpose in GroupAor E occupancies without first obtaining a permit in accordance with Section 105.6. _____1. Candles shall not be used in the building.
11/10/2010 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Replace the missing electrical outlet cover located behind the front counter.
11/10/2010 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. _____1. Repalce the missing ceiling tiles located in the water heater closet. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
11/10/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and mount all portable fire extingusihers.
11/10/2010 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1028.8 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. _____1. Remove the thumb-turn lock from the exit door located in the back room. NOTE: Panic hardware shall be the only locking device on the door.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02378
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/10/2010 INSP - FULL JBURGE Approved Correct all noted Tucson Fire Code violations.