Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T10FR02377
Case Details
Entered Date:
11/10/2010
Applicant:
ORCHARDS AT ARIZONA II LLC
Description:
Full Fire Prevention Inspection. Blancol--- 400-4359
Outstanding Inspections
Case Number: T10FR02377
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2010 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | IFC 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. _____1. Remove all storage located around the water heater in the back room. |
11/10/2010 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Replace the missing electrical outlet cover located behind the "Die Hard Arcade Game." |
11/10/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and mount the portable fire extinguisher located in the back room. |
11/10/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. _____1. The South EXIT sign located above the entrance door shall be internally illuminated. _____2. The North EXIT sign shall be internally illuminated. |
11/10/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.8 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. _____1. Remove the thumb-turn lock from the North exit door. NOTE: The panic hardware shall be the only locking device on the door. |
11/10/2010 | VIOL - DRY CLEANING | JBURGE | Correction Required | IFC 1205.1.5.3 Lint. Lint and refuse shall be removed from traps daily, deposited in approved waste cans, removed from the premises, and disposed of safely. At all other times, traps shall be held securely in place. _____1. Remove lint accumulation from all lint traps daily. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02377
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |