Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/04/2010

Applicant:

LEE FAMILY PROPERTY MANAGEMENT

Description:

Full Fire Prevention Inspection Building Rep: Tim McMullen Phone # 293-2421

Outstanding Inspections

Case Number: T10FR02330
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
11/04/2010 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
11/04/2010 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.6 Unapproved conditions Approved covers shall be provided for all switch and outlets. _____ Place approved cover(s) over the electrical switches (N & E wall)
11/04/2010 VIOL - MEANS OF EGRESS JLONGO Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Test and fix, repair, or replace any non-working emergency lighting unit(s) in order to meet code standards 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all non-working exit signs in order to meet code standards ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ___ ___ ___ ___________________ Passed on: ________ (Joseph P. Longo)