11/03/2010

Applicant:

ARIZONA BOARD OF REGENTS

Description:

Zachary's Pizza 10/28/10

Outstanding Inspections

Case Number: T10FR02307
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
11/03/2010 VIOL - FIRE SERVICE FEATURES MPursley Correction Required 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. _____Place sign on blocked door
11/03/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Repair wiring in dish room and cooler
11/03/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained. Maintain or remove non-required sprinkler system(appeal required for removal)
11/03/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, and/or replace the emergency lighting in order to meet code standards 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the pad locks and replace with an approved locking device such as, thumb turn lock or panic hardware on exit pathway. 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02307
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/17/2010 INSP - REINSPECTION MPursley Approved Still working on corrections, next RI due 12/28/10