Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

10/28/2010

Applicant:

ORCHARDS AT ARIZONA II LLC

Description:

Full Fire Prevention Inspection Building Rep: Sharon Tyssen Phone # 293-1663 / 293-1665

Outstanding Inspections

Case Number: T10FR02270
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
10/28/2010 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
10/28/2010 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlets. _____ Place approved cover(s) over the electrical outlet
10/28/2010 VIOL - FIRE RESIST.RATED CONST JLONGO Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ___ ___ ___ ___________________ Passed on: ________ (Joseph P. Longo)