Case: T10FR02213
Case Details
Entered Date:
10/25/2010
Applicant:
HIGH POINT ASSOCIATES & HECHT MILTON TR
Description:
Full Fire Prevention Inspection.
Outstanding Inspections
Case Number: T10FR02213
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6- Inspection, testing and maintenance. 1. Install a micro switch to automatically shut down electrical powerwhen the kitchen hood extinguishing system is activated. |
| 10/25/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 904.11.6.3- Cleaning. 1. Provide documentation of the hood system cleaning. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02213
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2010 | INSP - FULL | JBURGE | Approved | Correct all noted Tucson Fire Code violations. |