Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

10/21/2010

Applicant:

MAD DONALD HOLDING CORP & FREUND RENEE S

Description:

The Bagelry 10/19/10

Outstanding Inspections

Case Number: T10FR02189
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
VIOL - ADMINISTRATION None Not Inspected
10/21/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 105.6 Operational permits _____Have a permit for commercial oven
10/21/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Place approved cover(s) over the electrical boxes Repair broken conduit Repair lighting
10/21/2010 VIOL - FIRE RESIST.RATED CONST MPursley Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix and repair all openings or holes in the ceiling
10/21/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 609.2 Where required A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. _____Place extinguishing system over grill.
10/21/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag all portable fire extinguishers in order to meet code standards
10/21/2010 VIOL - COMPRESSED GASES MPursley Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times

Completed Inspections

Case Status: FIELD
Case Number: T10FR02189
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/02/2010 INSP - REINSPECTION MPursley Approved All other corrections made, has untill 12/14/10 to get plans to DSD.