Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/20/2010

Applicant:

GONZALES DANIEL & CELIA G 50% & OCHOA

Description:

Moreno tire shop fire inspection.

Outstanding Inspections

Case Number: T10FR02183
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
10/20/2010 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
10/20/2010 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation 308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction.
10/20/2010 VIOL - TIRE REBUILDING/STORAGE JLOYA Violation 2505.4 Distance from lot lines and buildings. Tire storage piles shall be located at least 50 feet (15 240 mm) from lot lines and buildings. Exception #1: For existing storage before August 4, 2004 individual piles not exceeding 5,000 square feet (464.5m²) of continuous area shall be located 10 feet (3048.3 mm) from buildings and lot lines for storage not exceeding 6 feet (1829 mm) in height. Exception #2: For existing storage before August 4, 2004 individual piles exceeding 6 feet (1829 mm) in height shall be located 20 feet (6096.6 mm) from buildings and lot lines.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02183
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/04/2010 INSP - REINSPECTION JLOYA Approved Tires movrd away from fence line and lp tank removed.