Case: T10FR02183
Case Details
Entered Date:
10/20/2010
Applicant:
GONZALES DANIEL & CELIA G 50% & OCHOA
Description:
Moreno tire shop fire inspection.
Outstanding Inspections
Case Number: T10FR02183
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2010 | INSP - FULL | JLOYA | Violation | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
| 10/20/2010 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction. |
| 10/20/2010 | VIOL - TIRE REBUILDING/STORAGE | JLOYA | Violation | 2505.4 Distance from lot lines and buildings. Tire storage piles shall be located at least 50 feet (15 240 mm) from lot lines and buildings. Exception #1: For existing storage before August 4, 2004 individual piles not exceeding 5,000 square feet (464.5m²) of continuous area shall be located 10 feet (3048.3 mm) from buildings and lot lines for storage not exceeding 6 feet (1829 mm) in height. Exception #2: For existing storage before August 4, 2004 individual piles exceeding 6 feet (1829 mm) in height shall be located 20 feet (6096.6 mm) from buildings and lot lines. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02183
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2010 | INSP - REINSPECTION | JLOYA | Approved | Tires movrd away from fence line and lp tank removed. |