Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

10/20/2010

Applicant:

SAINT AUGUSTINE CATHEDRAL ROMAN

Description:

St Augustine fire inspection.

Outstanding Inspections

Case Number: T10FR02167
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
10/20/2010 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation 308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction.
10/20/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panel board shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. ***Provide such signage.
10/20/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
10/20/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment.
10/20/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
10/20/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
10/20/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace emergency lighting
10/20/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1011.1 Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. ___ Sacristy locker room.
10/20/2010 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building.

Completed Inspections

Case Status: FIELD
Case Number: T10FR02167
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/20/2010 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________