Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T10FR02031
Case Details
Entered Date:
10/04/2010
Applicant:
TANQUE VERDE CENTER LLC
Description:
Full inspection done 10/1/2010; Gloria Allen - 885-8884; "B" occupancy; NOTE: All chemical cleaning is sent to a different "Main" location.
Outstanding Inspections
Case Number: T10FR02031
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/04/2010 | INSP - FULL | BCOBB | Violation | Please correct the following Tucson Fire Code violations: |
10/04/2010 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Extension cords: TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove or replace with approved fused power strip. |
10/04/2010 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Open wire boxes/ splices: TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ______Cover wires in an approved manner. |
10/04/2010 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Violation | Extinguishers not tagged / inspected: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code. |