Case: T10FR01947
Case Details
Entered Date:
09/21/2010
Applicant:
BELLA LUNA PROPERTIES LLC
Description:
SignAge 9/16/10
Outstanding Inspections
Case Number: T10FR01947
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/21/2010 | VIOL - FIRE SERVICE FEATURES | MPursley | Correction Required | 504.2 Maintenance of exterior doors and openings. _____Place sign on side door, "no exit" |
| 09/21/2010 | VIOL - BUILDING SVCS & SYSTEMS | MPursley | Correction Required | 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters. |
| 09/21/2010 | VIOL - FIRE RESIST.RATED CONST | MPursley | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile |
| 09/21/2010 | VIOL - FIRE PROTECTION SYSTEMS | MPursley | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag all portable fire extinguishers in order to meet code standards |
| 09/21/2010 | VIOL - MEANS OF EGRESS | MPursley | Correction Required | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… -- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: -- 2.1. The locking device is readily distinguishable as locked, -- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main egress door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01947
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2010 | COMPL - REINSPECTION | MPursley | Approved | All corrections made 10/5/10 |