Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T10FR01946
Case Details
Entered Date:
09/21/2010
Applicant:
ZETA PARTNERSHIP
Description:
Nail Supply Depot 9/16/10
Outstanding Inspections
Case Number: T10FR01946
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2010 | VIOL - PRECAUTION AGAINST FIRE | MPursley | Correction Required | 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code. |
09/21/2010 | VIOL - EMERGENCY PLAN/PREPARE | MPursley | Correction Required | 407.2 Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. |
09/21/2010 | VIOL - BUILDING SVCS & SYSTEMS | MPursley | Correction Required | 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters. |
09/21/2010 | VIOL - MEANS OF EGRESS | MPursley | Correction Required | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… -- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: -- 2.1. The locking device is readily distinguishable as locked, -- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main egress door. |
09/21/2010 | VIOL - HAZARDOUS MATERIALS,GEN | MPursley | Correction Required | 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. _____Place NFPA 704 marking on front and back of store 2703.1 Maximum Allowable Quantities: Class IB Flammable liquids: 120gal. can be doubled with proper cabinet and doubled again if sprinklered. _____Remove excess Flammable Liquids. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01946
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2010 | INSP - REINSPECTION | MPursley | Approved | All corrections made 10/28/10 |