Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/20/2010

Applicant:

ST DEMETRIOS GREEK ORTHODOX CHURCH INC

Description:

Full Fire Prevention Inspection.

Outstanding Inspections

Case Number: T10FR01942
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
09/20/2010 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1006.1- Emergency illumination. 1. The northwest exit sign located in the church hall shall have emergency back-up power.
09/20/2010 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1011.5.2- Exit sign illumination. 1. The northwest exit sign located in the church shall be fully illuminated at all times. NOTE: One of the two bulbs has burned out and no longer illuminates the sign.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01942
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/23/2010 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.