Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T10FR01937
Case Details
Entered Date:
09/16/2010
Applicant:
KWAN HIU LAM & KWAN HON LAM & MING
Description:
Chavez Upholstery 9/14/10
Outstanding Inspections
Case Number: T10FR01937
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2010 | VIOL - PRECAUTION AGAINST FIRE | MPursley | Correction Required | 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code. |
| 09/16/2010 | VIOL - FIRE PROTECTION SYSTEMS | MPursley | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag all portable fire extinguishers in order to meet code standards |
| 09/16/2010 | VIOL - MEANS OF EGRESS | MPursley | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the security door or change lock and fix doors so they will open properly 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… -- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: -- 2.1. The locking device is readily distinguishable as locked, -- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main egress door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01937
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2010 | INSP - REINSPECTION | MPursley | Approved | Dropped off appeal for back door on 8/13/10. All corrections made 9/13/10. |