Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

09/15/2010

Applicant:

KIM SUK HOO & MYUNG SOO CP/S

Description:

Full Fire Prevention Inspection Building Rep: Patrick Forsythe Phone # 270-6128

Outstanding Inspections

Case Number: T10FR01935
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
09/15/2010 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. *** NOTE *** 904.11.5 Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
09/15/2010 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed or replace with an approved fused power strips. 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlets. _____ Place approved cover(s) over the electrical outlet (prep area)
09/15/2010 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Have your 12 year hydro test done to your hood exstinguishing system. _____ re-adjust your hood system's nozzels to maintain proper coverage of your commercial cooking equipment. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ____ properly hang all protable fire extinguishers according to code.
09/15/2010 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ remove the drop bar system from your rear egress door.
09/15/2010 VIOL - COMPRESSED GASES JLONGO Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ___ ___ ___ ___________________ Passed on: ________ (Joseph P. Longo)