Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/09/2010

Applicant:

MONTEREY WATER COMPANY

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T10FR01894
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
09/09/2010 VIOL - MEANS OF EGRESS WMOTTO Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1___ NEED TO REMOVE KEYED LOCK ON REAR EXIT DOOR.
09/09/2010 VIOL - MEANS OF EGRESS WMOTTO Correction Required 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. 1___ NEED TO HAVE A CLEAR PATHWAY TO REAR EXIT DOOR. DOOR MUST NOT BE BLOCKED

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01894
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/29/2010 INSP - FULL WMOTTO Approved VIOLATION ABATED.