Case: T10FR01891
Case Details
Entered Date:
09/09/2010
Applicant:
BROWN GAROLD C FAMILY LTD PARTNERSHIP
Description:
WestMed Fire inspection.
Outstanding Inspections
Case Number: T10FR01891
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
09/09/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |
09/09/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. ___Provide copy of last sprinkler inspection report. |
09/09/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.1 Where required. Portable fire extinguishers shall be installed in the following locations: 1. In all Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. ____ Distance from one fire extinguisher to another shall not be more than 75 feet |
Completed Inspections
Case Status: FIELD
Case Number: T10FR01891
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2010 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |