Case: T10FR01851
Case Details
Entered Date:
08/30/2010
Applicant:
29-49 N SCOTT LLC
Description:
Full Fire Prevention Inspection. Travis Reese 624-4747
Outstanding Inspections
Case Number: T10FR01851
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1. Appliances shall be properly covered under the hood system. 2. Service the hood extinguishing system. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01851
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |