Case: T10FR01850
Case Details
Entered Date:
08/30/2010
Applicant:
T C REAL ESTATE LLC
Description:
Full Fire Prevention Inspection Jackie Owens 887-8770
Outstanding Inspections
Case Number: T10FR01850
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6- Inspection, Testing and Maintenance. 1. Repair all noted deficiencies on the hood extinguishing system inspection report. NOTE: The system is lacking the required coverage. |
08/30/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1011.2- Exit signs. 1. THe exit sign located in the back room shall be fully illuminated. NOTE: One bulb is not illuminated. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01850
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/20/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |