Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/30/2010

Applicant:

GEE PROPERTIES-3 LLC

Description:

AZ Hatters 8/25/10

Outstanding Inspections

Case Number: T10FR01849
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
08/30/2010 VIOL - FIRE SERVICE FEATURES MPURSLEY Correction Required 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____Keep riser area clear
08/30/2010 VIOL - BUILDING SVCS & SYSTEMS MPURSLEY Correction Required 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips.
08/30/2010 VIOL - MEANS OF EGRESS MPURSLEY Correction Required 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… -- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: -- 2.1. The locking device is readily distinguishable as locked, -- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main egress door.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01849
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/10/2010 COMPL - REINSPECTION MPursley Approved All corrections made 9/8/10