Description:

Full Fire Prevention Inspection Building Rep: Johnny Ray Rogers Phone # 887-2919 / 990-0357

Outstanding Inspections

Case Number: T10FR01828
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
08/25/2010 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
08/25/2010 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Place approved cover(s) over the electrical outlets throughout the building.
08/25/2010 VIOL - FIRE RESIST.RATED CONST JLONGO Correction Required 703.1 Maintenance The required fire-resistance-rated construction shall be maintained. Such elements shall be repaired, restored, or replaced when damaged, altered, breached, or penetrated. _____ Fix, repair, or restore all openings or holes in the fire resistive walls
08/25/2010 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from all associated doors, as bolt lock of any kind are not permitted. 1027.8 Opening force for doors. The opening force for interior side-swinging doors without closers shall not exceed a 5-pound (22 N) force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a force of not more than 15 pounds (66 N). _____ Repair the inoperable door ( S/W door ) ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ___ ___ ___ ___________________ Passed on: ________ (Joseph P. Longo)