Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

08/24/2010

Applicant:

CITY OF TUCSON

Description:

MAITS inspections

Outstanding Inspections

Case Number: T10FR01800
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 19
End Date Description Inspector Results Comments
VIOL - FIRE PROTECTION SYSTEMS None Not Inspected
VIOL - FLAMMABLE LIQUIDS None Not Inspected
08/24/2010 INSP - FULL BCORRALE Continued Full MAITS inspection for the Reid Park zoo, Tucson Zoological society, Zoo admin. and zoo concessions.
08/24/2010 VIOL - PRECAUTION AGAINST FIRE BCORRALE Continued Electrical panels blocked. (2) IFC 2006 CHAP. 3 Unblock panels.
08/24/2010 VIOL - PRECAUTION AGAINST FIRE BCORRALE Continued Storage in buildings very disorderly, with no aisle for egress. IFC 2006 315.2 STORAGE IN BUILDINGS (2) ___Clear storage and maintain an aisle of no less then 36 in. wide.
08/24/2010 VIOL - FIRE SERVICE FEATURES BCORRALE Continued Sprinkler risers blocked. IFC 2006 CHAP. 5 Unblock risers, ensure 3-ft. clearance at all times.
08/24/2010 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Continued Electrical cords knotted, bent. IFC 2006 605.1 Repair cords.
08/24/2010 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Continued Extension cords in place of permanent wiring. (9) IFC 2006 605.5 Remove cords, use permanent receptacles.
08/24/2010 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Continued Frayed electrical wiring to appliances. (2) IFC 2006 605.1 Repair wiring.
08/24/2010 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Continued Outlet covers missing. (2) IFC 2006 605.1 Replace covers.
08/24/2010 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Continued Unapproved multiplig adapters in use. (3) IFC 2006 605.4 Remove, replace with listed adapters.
08/24/2010 VIOL - FIRE RESIST.RATED CONST BCORRALE Continued Ceiling tile damaged. (2) IFC 2006 703.1 MAINTINANCE OF FIRE RESISTIVE CONSTRUCTION Replace ceiling tile.
08/24/2010 VIOL - FIRE RESIST.RATED CONST BCORRALE Continued Fire door missing self closing mechanism, being held open. IFC 2006 703.2.3 Repair immediately
08/24/2010 VIOL - MEANS OF EGRESS BCORRALE Continued
08/24/2010 VIOL - MEANS OF EGRESS BCORRALE Continued Emergency lighting out of service. IFC 2006 CHAP. 10 Repair lighting.
08/24/2010 VIOL - MEANS OF EGRESS BCORRALE Continued Exit signs our of service. IFC 2006 CHAP. 10 Repair signs.
08/24/2010 VIOL - COMPRESSED GASES BCORRALE Continued Unsecured cylinders (3) IFC 2006 3303.5.3 Secure cylinders.
08/24/2010 VIOL - TOXIC MATERIALS BCORRALE Continued Placarding for building needed for hazardous materials. IFC 2006 CHAP. 37 Install NFPA 704 for ammonium sulfate.
08/24/2010 VIOL - TOXIC MATERIALS BCORRALE Continued Placarding for ramada area needed for hazardous materials. IFC 2006 CHAP. 37 Install NFPA 704 for ammonium sulfate.