Case: T10FR01795
Case Details
Entered Date:
08/24/2010
Applicant:
NORTH FOURTH LLC
Description:
Full Fire Prevention Inspection/Stop Work Order Micah Blatt------ 444-4735 or 623-3711
Outstanding Inspections
Case Number: T10FR01795
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2010 | VIOL - ADMINISTRATION | JBURGE | Correction Required | IFC 111.1 Order. Whenever the fire code official finds any work regulated by this code being performed in a manner contrary to the provisions of this code or in a dangerous or unsafe manner, the fire code official is authorized to issue a stop work order. _____1. Remove all propane cylinders from the building. EXCEPTION: One 5 gallon propane cylinder is allowed at the front work station. _____2. Remove all oxygen cylinders from the building. EXCEPTION: 1 oxygen cylinder is allowed at the fron work station. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01795
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |