Case: T10FR01793
Case Details
Entered Date:
08/23/2010
Applicant:
HALLE PROPERTIES LLC
Description:
Inspection
Outstanding Inspections
Case Number: T10FR01793
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2010 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Tire storage too close to ceiling. |
| 08/23/2010 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Ceiling light fixture in tire storage area. |
| 08/23/2010 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1014.4.1 Aisles in tire storage area. |
| 08/23/2010 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.5 Emergency light |
| 08/23/2010 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.5 Emergency lights |
| 08/23/2010 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.2 Exit blocked at SE exit from service area. |
| 08/23/2010 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.4 Exit signs |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01793
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2010 | INSP - FULL | TKNAPP | Approved |