Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/18/2010

Applicant:

KWAN HIU LAM & KWAN HON LAM & MING

Description:

The Letter Box 8/2/10

Outstanding Inspections

Case Number: T10FR01771
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
08/18/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained.
08/18/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the double-keyed lock and replace with an approved locking device such as, thumb turn lock or panic hardware on employee side door, and drop bar on back door.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01771
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/05/2010 INSP - REINSPECTION MPursley Approved All corrections made 11/4/10