Case: T10FR01743
Case Details
Entered Date:
08/17/2010
Applicant:
KWAN HIU LAM & KWAN HON LAM & MING
Description:
Phil's Cafe 8/13/10
Outstanding Inspections
Case Number: T10FR01743
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2010 | VIOL - PRECAUTION AGAINST FIRE | MPursley | Correction Required | 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code. |
| 08/17/2010 | VIOL - FIRE RESIST.RATED CONST | MPursley | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile |
| 08/17/2010 | VIOL - FIRE PROTECTION SYSTEMS | MPursley | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained: K-extinguisher,old extinguisher, hood system inspection, and proper coverage. |
| 08/17/2010 | VIOL - MEANS OF EGRESS | MPursley | Correction Required | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the ---- egress door, as bolt lock of any kind are not permitted |
| 09/08/2010 | INSP - REINSPECTION | MPursley | Correction Required | Stopped by to drop off pre-cite and the building has been vacated 9/7/10 |