Case: T10FR01720
Case Details
Entered Date:
08/16/2010
Applicant:
CITY SURF MANAGEMENT GROUP LLC
Description:
Fire call-out/ Sprinkler system OOS/ Red Tag Robby Anderson----609-3644
Outstanding Inspections
Case Number: T10FR01720
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2010 | INSP - LIFE SAFETY | JBURGE | Correction Required | Fire Call-out/ Sprinkler system OOS/ Red Tagged Cooking system. |
| 08/16/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.9 Inspection, testing and maintenance. 1. The automatic sprinkler system shall be repaired and placed back in service before the restaurant is open to the public. FIRE WATCH HAS BEEN ESTABLISHED. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01720
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2010 | VIOL - ADMINISTRATION | JBURGE | Approved | The automatic sprinkler system was repaired and placed back in service. The hood system was repaired and approved to operate by a mechanical Inspector. Red tags were removed. |