Case: T10FR01701
Case Details
Entered Date:
08/12/2010
Applicant:
ABCO CDC LLC
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T10FR01701
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2010 | INSP - FULL | WMOTTO | Correction Required | CORRECT TUCSON FIRE CODE VIOLATIONS. |
08/12/2010 | VIOL - PRECAUTION AGAINST FIRE | WMOTTO | Correction Required | 315.3 Outside storage. Outside storage of combustible materials shall not be located within 10 feet (3048 mm) of a property line. Exceptions: 1. The separation distance is allowed to be reduced to 3 feet (914 mm) for storage not exceeding 6 feet (1829 mm) in height. 1___ NEED TO STORE PROPANE OUTSIDE OF BUILDING 10 FEET FROM BUILDING. |
08/12/2010 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1___ NEED TO PROVIDE SPRINKLER REPORT SHOWING SYSTEM HAS BEEN SERVICED WITHIN THE YEAR. 2___ NEED TO REMOVE ICE BUILD UP ON SPRINKLER HEAD IN EAST FREEZER IN MEAT MARKET. |
08/12/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1___ NEED TO REMOVE SLIDE BAR AND HARDWARE FROM DOORS IN LOADING FOOD STORAGE AREA. |
08/12/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 1. Places of detention or restraint. 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revocable by the fire code official for due cause. 3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface- mounted hardware. 4. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt or security chain, provided such devices are openable from the inside without the use of a key or tool. 1___ SIGN OVER MAIN FRONT DOORS STATING DOORS REMAIN UNLOCKED DURING BUISNESS HOURS. |
08/12/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. 1___ REAR EXIT DOOR IN MEAT MARKET WAS BLOCKED BY MEAT TRAYS KEEP CLEAR AT ALL TIMES. |
08/12/2010 | VIOL - COMPRESSED GASES | WMOTTO | Correction Required | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. 1___ NEED TO SECURE HELIUM BOTTLE TO WALL OR SHELVES BY CHAIN OR STRAPS TO PREVENT FALLING. |