Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/11/2010

Applicant:

FONES FAMILY TRUST

Description:

FULL INSPECTION

Outstanding Inspections

Case Number: T10FR01693
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
08/11/2010 INSP - FULL JDAVIS Correction Required 1. _____ 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. - CONDUIT AND ELECTRICAL OUTLET BEHIAND THE STORAGE SHED SHALL BE ABATED TO MEET THE ELECTRICAL CODE - REPLACE THE ELECTRICAL COVERPLATE INSIDE THE STORAGE SHED 2. _____ 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. HEALTH =2 fLAMMABILTY = 1 REACTIVITY = 0 2.