Case: T10FR01646
Case Details
Entered Date:
08/09/2010
Applicant:
LLJ HOLDINGS LLLP
Description:
FULL INSPECTION
Outstanding Inspections
Case Number: T10FR01646
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2010 | INSP - FULL | jdavis | Correction Required | 1. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. - NEAR TROPHY DESK - UNDER TROHPY DISPLAY 2. _____ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used: - REAR OFFICE (LIGHTSWITCH) - WALL NEAR REAR EXIT (3 EA) - STORAGE ROOM (LIGHTSWITCH COVER) - 3 EA IN STORAGE ROOM 3. _____ 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. -TWO EACH ON REAR EXIT |