Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T10FR01634
Case Details
Entered Date:
08/06/2010
Applicant:
MIDVALE MARKETPLACE LLC
Description:
Hamburger Stand fire inspection.
Outstanding Inspections
Case Number: T10FR01634
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels |
08/06/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. ***The hood exhaust and extinguishing systems shall be inspected and tagged |
08/06/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. |
08/06/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01634
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2010 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
08/24/2010 | INSP - REINSPECTION | JLOYA | Approved | Violations abated. |