Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/06/2010

Applicant:

MIDVALE MARKETPLACE LLC

Description:

Subway Fire inspection.

Outstanding Inspections

Case Number: T10FR01633
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
08/06/2010 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
08/06/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
08/06/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace emergency lighting
08/06/2010 VIOL - COMPRESSED GASES JLOYA Violation 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel. *** Secure gas cylinder in an approved manner to avoid accidental dislodgment.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01633
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/24/2010 INSP - REINSPECTION JLOYA Approved Violations abated.