Description:

Arby's fire inspection.

Outstanding Inspections

Case Number: T10FR01592
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
08/03/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace emergency lighting
08/03/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01592
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
08/03/2010 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
08/05/2010 INSP - REINSPECTION JLOYA Approved Violations abated.