Case: T10FR01571
Case Details
Entered Date:
08/02/2010
Applicant:
CAMPBELL SHOPS LLC
Description:
Patio Pools & Spas 7/29/10
Outstanding Inspections
Case Number: T10FR01571
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2010 | VIOL - PRECAUTION AGAINST FIRE | MPursley | Correction Required | 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code. |
| 08/02/2010 | VIOL - BUILDING SVCS & SYSTEMS | MPursley | Correction Required | 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters. |
| 08/02/2010 | VIOL - FIRE PROTECTION SYSTEMS | MPursley | Correction Required | 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ Service, tag, maintain, and properly hang all portable fire extinguishers according to code |
| 08/02/2010 | VIOL - MEANS OF EGRESS | MPursley | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the double-keyed lock and replace with an approved locking device such as, thumb turn lock or panic hardware 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions and be sure to always maintain a clear and obstruction free path to your |
| 08/02/2010 | VIOL - HAZARDOUS MATERIALS,GEN | MPursley | Correction Required | 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. _____Place NFPA 704 markings on front doors. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01571
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2010 | INSP - REINSPECTION | MPursley | Approved | All corrections made 9/28/10 |