Description:

SELF INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01438
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 2
End Date Description Inspector Results Comments
09/09/2010 INSP - SELF INSPECTION PROGRAM NSPRENGE Approved RI - 9/23
09/09/2010 INSP - SELF INSPECTION PROGRAM NSPRENGE Approved 1. 901.6 - No record of sprinkler report since 2006. 2. Needs NFPA Diamond on door to closet that houses x ray developer and x ray fixer liquids. 8 gallons combined total of stored liquids. No flammability rating. Heath hazard and Reactivity only. 3. Butterfly valve to sprinkler riser is not secured. 4. Missing head wrench in sprinkler head box next to Riser.