FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T10FR01367
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2010 | VIOL - FIRE RESIST.RATED CONST | WMOTTO | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. 1___ REPLACE CEILING TILES IN KITCHEN. |
07/15/2010 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1___ SHOW REPORT SPRINKLER SYSTEM HAS BEEN SERVICED WITH THE YEAR. FIX DEFICIENCIES. |
07/15/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system 1___ REPAIR EMERGENCY LIGHT NEAR SODA MACHINE. |
07/15/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. 1___ REPAIR EXIT SIGN OVER SOUTH EXIT DOOR. 2___ REPAIR EXIT SIGN OVER WEST EXIT DOOR. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01367
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2010 | INSP - FULL | WMOTTO | Approved | ALL VIOLATIONS CORRECTED. |