Case: T10FR01328
Case Details
Entered Date:
07/14/2010
Applicant:
TAVEL FAMILY LIMITED PARTNERSHIP LLP
Description:
Asadero Sonora fire inspection.
Outstanding Inspections
Case Number: T10FR01328
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes __Cover empty slots at breaker panel. |
| 07/14/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 904.11.5.2 Class K portable fire extinguishers for deep fat fryers. When hazard areas include deep fat fryers, listed Class K portable fire extinguishers shall be provided |
| 07/14/2010 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.2 Door swing. Egress doors shall be side-hinged swinging. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01328
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2010 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
| 07/30/2010 | INSP - REINSPECTION | JLOYA | Approved | Violations abated. |