Case: T10FR01325
Case Details
Entered Date:
07/13/2010
Applicant:
MACHADO JOSEPH JAMES 1/3 & MACHADO
Description:
Full Fire Prevention Inspection. Kiara Duarte 292-9797
Outstanding Inspections
Case Number: T10FR01325
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/13/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. Clean and remove all grease accumulation from the kitchen hood exhaust system. NOTE: PROVIDE DOCUMENTATION OF THE CLEANING. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
07/13/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1. Remove the slide bolt from the south egress door in the kitchen and replace it with a thumb-turn deadbolt. |
07/13/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the broken emergency lighting unit located above the office door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01325
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violatins have been corrected. |