Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

07/09/2010

Applicant:

PARK MALL LLC

Description:

Full Inspection conducted 07/07/10 I have received a copy of this report and understand the corrections needed: ______________ Business Rep.: Ly Yam, Phone: 514-5738 Inspector: _________________, David Greenleaf, MA 23 If you have any questions please call 791-4502. Approved: ________ Re-inspection: __/__/__ (or after) Certificate of Occupancy: On File with inaccuracies* *Occupant Load: 0 (690sft. in Occ Group: B, OL=6) Please correct the following Tucson Fire Code violations:

Outstanding Inspections

Case Number: T10FR01303
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
07/07/2010 INSP - FULL dgreenl1 Violation TFC 904.11.5 - Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. _____ Install a Class-K extinguisher. TFC 904.11.6.3 - Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____ Clean hood system, specifically grease channel and catch pans. TFC 904.11.6.4 - Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. _____ Have hood extinguishing system professionally serviced and tagged. Provide a copy of the report. If system has been serviced in last 6 months… _____ Provide a copy of your most recent hood system report. Blocked electrical panel: TFC 605.3 - Working space and clearance. A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels so that doors open freely. TFC 107.1 - Maintenance of safeguards. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards. _____ Exit Sign Illumination _____ Repair Emergency Light TFC 703.1 - Maintenance The required fire-resistance rating of fire-resistance-rated construction... shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated... _____ Replace ceiling tiles that have been moved.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01303
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/02/2010 INSP - REINSPECTION dgreenl1 Approved