Case: T10FR01257
Case Details
Entered Date:
06/25/2010
Applicant:
CORTES FRANK B SR & MARIA C
Description:
Elite auto tint.
Outstanding Inspections
Case Number: T10FR01257
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2010 | VIOL - FIRE SERVICE FEATURES | JLOYA | Violation | 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. |
| 06/25/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. |
| 06/25/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
| 06/25/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |
| 06/25/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 shall be installed so that its top is not more than 5 feet above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds shall be installed so that its top is not more than 3.5 feet above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches. _____ Mount extinguishers in an approved manner |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01257
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2010 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
| 07/09/2010 | INSP - REINSPECTION | JLOYA | Approved | Violations abated. |