Case: T10FR01223
Case Details
Entered Date:
06/18/2010
Applicant:
PIMA COUNTY
Description:
Full Inspection for "County" CofO
Outstanding Inspections
Case Number: T10FR01223
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2010 | VIOL - FIRE SERVICE FEATURES | GDAURIA | Violation | TFC 505.1 Address numbers-PREMISES IDENTIFICATION Install address numbers @ all side and rear doors Install address numbers @ SE Entry doors |
06/18/2010 | VIOL - FIRE SERVICE FEATURES | GDAURIA | Violation | TFC 506.1 KEY BOXES- Where required. Install approved TFD Lock Box @ main entrance |
06/18/2010 | VIOL - BUILDING SVCS & SYSTEMS | GDAURIA | Violation | TFC 605.3.1-ELECTRICAL-Labeling. Instal "Electrical Room" sign Label all electrical panels (all breakers) (P4, P5) All remaining electrical to be done by licensed electrician |
06/18/2010 | VIOL - FIRE RESIST.RATED CONST | GDAURIA | Violation | TFC 703.1 FIRE-RESISTANCE-RATED CONSTRUCTION All ceiling tiles must be in place Firestop ceiling in electrical room |
06/18/2010 | VIOL - FIRE PROTECTION SYSTEMS | GDAURIA | Violation | TFC 906.1 Extinguishers Portable extinguishers to be tested and tagged annually |
06/18/2010 | VIOL - FIRE PROTECTION SYSTEMS | GDAURIA | Violation | TFC 912.4 Signs - FIRE DEPARTMENT CONNECTIONS Instal "FDC" sign @ NW door (exterior) Paint sprinkler bell (red) @ NW corner (for visibility) |
06/18/2010 | VIOL - MEANS OF EGRESS | GDAURIA | Violation | TFC 1006.1 ILLUMINATION- MEANS OF EGRESS Illumination req. Verify that emergency egress lighting kis in warehouse functions properly Verify that emergency egress lighting in all areas is provided by an isolated lighting circuit throughout and that it functions properly (including bathrooms) |
06/18/2010 | VIOL - MEANS OF EGRESS | GDAURIA | Violation | TFC 1011.1 EXIT SIGNS-Where required. Install illuminated exit signs as discussed (6) Install "Not an Exit" signs (3) @ entry to warehouse |