Case: T10FR01210
Case Details
Entered Date:
06/17/2010
Applicant:
GS PROPERTY INVESTMENTS LLC
Description:
Dollar Tree fire inspection.
Outstanding Inspections
Case Number: T10FR01210
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels |
| 06/17/2010 | VIOL - FIRE RESIST.RATED CONST | JLOYA | Violation | 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles. |
| 06/17/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. ___Provide copy of last sprinkler inspection report. |
| 06/17/2010 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01210
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2010 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
| 11/23/2010 | INSP - REINSPECTION | JLOYA | Approved | Violations abated. |