Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/17/2010

Applicant:

SES PROPERTIES LP

Description:

Goldberg and Osborne fire inspection.

Outstanding Inspections

Case Number: T10FR01202
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
06/17/2010 VIOL - EMERGENCY PLAN/PREPARE JLOYA Violation 407.2 Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises.
06/17/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
06/17/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01202
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
06/17/2010 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
07/01/2010 INSP - REINSPECTION JLOYA Approved Violations abated.