Case: T10FR01172
Case Details
Entered Date:
06/15/2010
Applicant:
T C REAL ESTATE LLC
Description:
Jack in the Box fire inspection.
Outstanding Inspections
Case Number: T10FR01172
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2010 | VIOL - EMERGENCY PLAN/PREPARE | JLOYA | Violation | 407.2 Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. |
| 06/15/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels |
| 06/15/2010 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1014.4.1 - Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches. Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches in width. |
| 06/15/2010 | VIOL - COMPRESSED GASES | JLOYA | Violation | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01172
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2010 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
| 07/01/2010 | INSP - REINSPECTION | JLOYA | Approved | Violations abated. |