Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/11/2010

Applicant:

CITIZEN PRINTING LLC

Description:

Miles Ahead Cyclery 6/9/10

Outstanding Inspections

Case Number: T10FR01153
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
06/11/2010 VIOL - FIRE SERVICE FEATURES MPursley Correction Required 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. _____Place signs on extra door: outside, "this door blocked" and inside, "not an exit"
06/11/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained.
06/11/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the ---- egress door, as bolt lock of any kind are not permitted 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____ The front main entrance door secondary locking device shall be disabled or replaced to meet code standards. I.E. the lock shall release when twisted from the interior side.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01153
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/29/2010 INSP - REINSPECTION MPursley Approved All corrections made 7/28/10