Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/08/2010

Applicant:

COMANCHE WELLS MOBILE HOME PARK

Description:

Full Fire Prevention Inspection Building Rep: Carol Pine Phone # 888-4150

Outstanding Inspections

Case Number: T10FR01116
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
06/08/2010 INSP - FULL JLONGO Correction Required 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment. Extinguishing system units shall be weighed and the required amount of agent verified. Stored pressure-type units shall be checked for the required pressure. The cartridge of cartridge-operated units shall be weighed and replaced at intervals indicated by the manufacturer. 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Sevice and Tag your hood extinguishing system as it is over due. _____ Have your hood extinguishing system hydrostatically test for its 12 year. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) ___________________ Passed on: ________ (Joseph P. Longo)