Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/03/2010

Applicant:

WRI SHOPPES AT BEARS PATH LLC

Description:

Mayfield Flowers 6/1/10

Outstanding Inspections

Case Number: T10FR01083
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
06/03/2010 VIOL - PRECAUTION AGAINST FIRE MPursley Correction Required 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code.
06/03/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove extension cords605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Place approved cover(s) over the electrical … .
06/03/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag all portable fire extinguishers in order to meet code standards

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01083
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/29/2010 INSP - REINSPECTION MPursley Approved All corrections made 7/28/10