Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/02/2010

Applicant:

WEINGARTEN NOSTAT INC

Description:

Pizza Hut 6/1/10

Outstanding Inspections

Case Number: T10FR01070
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
06/02/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____ The hood system in your building has been found unfit and requires a cleaning. You are to have your hood system cleaned immediately and provide the proper paper work to prove that the required cleaning has been done professionally.
06/02/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). 3. No additional locks or latches shall be added

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01070
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/16/2010 INSP - REINSPECTION MPursley Approved Fryer hood looked good, all corrections made 9/14/10