Case: T10FR01068
Case Details
Entered Date:
06/02/2010
Applicant:
LPR PROPERTIES LLC
Description:
Full Fire Prevention Inspection. Bruce Alflen 292-0314
Outstanding Inspections
Case Number: T10FR01068
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Add a hood extinguishing system nozzle to properly cover both deep fat fryers. |
| 06/02/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.8 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. _____1. Remove the double keyed lock from the exterior door with panic hardware located in the kitchen. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01068
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violatoins have been corrected. **** The owner removed the panic hardware from the kitchen exterior door. She was informed to replace the required hardware ***** |