Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/27/2010

Applicant:

TUCSON AZ (JENSEN-HOROWITZ/DICKEY) LLC

Description:

Walgreens 5/26/10

Outstanding Inspections

Case Number: T10FR01056
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
05/27/2010 VIOL - FIRE SERVICE FEATURES MPursley Correction Required 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. ____keep the riser clear
05/27/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, and/or replace the emergency lighting in order to meet code standards 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01056
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/11/2010 COMPL - REINSPECTION MPursley Approved All corrections made 6/10/10